Safe 29 Emergency Light TWT2981K

220-240 V 50/60 Hz AC, DC
IP 65
RAL 9003
650 °C
EN 1838
EN 60598-2-22

Addressable 230 V centrally supplied emergency light

Safe 29 is suited for demanding environmental conditions. It has a plastic frame, and combines functional design with a high protection rating. For emergency lighting applications, an 18 W model is also available. It allows a higher mounting height. The double insulated construction material is of shock-resistant plastic. Safe 29 is available with either a long-life LEDs, or a fluorescent lamp. The luminaires in the Safe 29 product line are suited for interior and exterior applications.

Thanks to the improved LED technology, the new ESCAP models are now available, offering longer mounting distance for both open area (TWS2992WAC) and escape routes (TWS2992WAB). With these new ESCAP models, also 4 m mounting height is now possible.

Product CodeTWT2981K
FeatureIntelligent Controller, Tapsa Control
Mounting (standard)ceiling, wall, surface
Mounting (optional)recess
Customs Code94056080
GTIN Code6438045006390
ETIM Product ClassEC001957
Length341 mm
Width94 mm
Height189 mm
Weight1,2 kg
Max Input Power VA15,5 VA
Max Input Power W13,5 W
Nominal Supply Voltage220-240 V, 50/60 Hz AC, DC
Protection ClassII
IP ClassIP65
Temperature Range Min - Max-10...+50 °C
Glow Wire Test of Plastic Materials650 °C
Light Source11W/840/4P 2G7
Body Materialplastic
Aperture for Recess Mounting350 x 215 mm
ColourRAL9003
Electrical Installation2/3 x 2,5 mm²
Luminous Flux540 lm

Emergency lighting for escape routes (ceiling mounting)

  • Table of 1 lux for escape routes in the middle line according to the norm EN 1838.
  • Level of measurement 0,02 m, measurement result with battery operation.
Y R1 R4 R2 X h
  • R1 distance from wall (X axis)
  • R2 installation distance between lights (X axis)
  • R4 distance from wall (Y axis)

TWT2981K

Mounting height (m)Below the light luxR1 (m)R2 (m)R4 (m)
1 lux1 lux1 lux
2,5145133
456153

Emergency lighting for open areas (ceiling mounting)

  • Table of 0,5 lux for open areas according to the norm EN 1838, 0,5 m edge district is considered in the table.
  • Level of measurement 0,02 m, measurement result with battery operation.
Y R1 R3 R2 X h R4
  • R1 distance from wall (X axis)
  • R2 installation distance between lights (X axis)
  • R3 installation distance between lights (Y axis)
  • R4 distance from wall (Y axis)

TWT2981K

Mounting height (m)Below the light luxR1 (m)R2 (m)R3 (m)R4 (m)
0,5 lux0,5 lux0,5 lux0,5 lux
2,5146,51263,5
457,51484,5

Optional accessories:

Shock Protecting Covers for Emergency Lights

Product CodeProduct NameCompatible Product GroupsAdd to offer basket
TW77510BShock protecting cover TW77510BESC 10 Emergency Exit Lights, DISCONTINUED: ESC 6L Emergency Exit Lights, ESC 29 Emergency Exit Lights, Safe 29 Emergency Lights, ESC 81 Emergency Exit Lights

Optional Mounting Accessories for Emergency Exit Lights

Product CodeProduct NameCompatible Product GroupsAdd to offer basket
XWT2904Ceiling bracket XWT2904Safe 29 Emergency Lights, ESC 29 Emergency Exit Lights

You may also be interested in these products:

Non-addressable 24 V Centrally Supplied Emergency Exit Lights

Product CodeNominal Supply VoltagePictogramPictogram InfoAdd to offer basket
TWT9041W24 V, 50/60 Hz AC, DC2-sided, 25 m
TWT8041W24 V, 50/60 Hz AC, DC2-sided, 20/26/30 m

Information and offers on Safe 29 Emergency Light TWT2981K