Trail Zone Lowbay emergency light TWTC271W

24-230 V 50/60 Hz AC, DC
LED
IP 20
RAL 9003
650 °C
EN 1838
EN 60598-2-22

24-230 V centrally supplied emergency light

Teknoware Trail is an elegant emergency light that is easy to install on a lighting track. Thanks to its unique design, it is suitable for direct mounting on common lighting track systems. The luminaire can also be mounted directly on the ceiling. Trail has a modern and streamlined appearance so it blends in with the surroundings and architecture. Trail’s wide product family and range of optics offer many options to suit a variety of applications and systems.

Trail Zone Lowbay is particularly suitable for low spaces. The luminaire provides a broad, uniform light pattern that illuminates open areas efficiently.
Teknoware Trail is an elegant emergency light that is easy to install on a lighting track. Thanks to its unique design, it is suitable for direct mounting on common lighting track systems. The luminaire can also be mounted directly on the ceiling. Trail has a modern and streamlined appearance so it blends in with the surroundings and architecture. Trail’s wide product family and range of optics offer many options to suit a variety of applications and systems.

Trail Zone Lowbay is particularly suitable for low spaces. The luminaire provides a broad, uniform light pattern that illuminates open areas efficiently.

Product CodeTWTC271W
Mounting (standard)ceiling, surface, rail
Customs Code94056080
GTIN Code6438045025155
Length345 mm
Width80 mm
Height48 mm
Weight0,9 kg
Max Input Power VA7,5 VA (24 V), 11 VA (230 V)
Max Input Power W4 W (24 V), 4 W (230 V)
Nominal Supply Voltage24-230 V, 50/60 Hz AC, DC
Protection ClassIII (24 V), I (230 V)
IP ClassIP20
Temperature Range Min - Max-30...+50 °C
Glow Wire Test of Plastic Materials650 °C
Light SourceLED
Body Materialmetal
ColourRAL9003
Electrical Installation2 x 2,5 mm² (24 V), 3 x 2,5 mm² (230 V)
Luminous Flux255 lm

Emergency lighting for escape routes (ceiling mounting)

  • Table of 1 lux for escape routes in the middle line according to the norm EN 1838.
  • Level of measurement 0,02 m, measurement result with battery operation.
Y R1 R4 R2 X h
  • R1 distance from wall (X axis)
  • R2 installation distance between lights (X axis)
  • R4 distance from wall (Y axis)

TWTC271W

Mounting height (m)Below the light luxR1 (m)R2 (m)R4 (m)
1 lux1 lux1 lux
2,54,35115
41,74144

Emergency lighting for open areas (ceiling mounting)

  • Table of 0,5 lux for open areas according to the norm EN 1838, 0,5 m edge district is considered in the table.
  • Level of measurement 0,02 m, measurement result with battery operation.
Y R1 R3 R2 X h R4
  • R1 distance from wall (X axis)
  • R2 installation distance between lights (X axis)
  • R3 installation distance between lights (Y axis)
  • R4 distance from wall (Y axis)

TWTC271W

Mounting height (m)Below the light luxR1 (m)R2 (m)R3 (m)R4 (m)
0,5 lux0,5 lux0,5 lux0,5 lux
2,54,35,510105,5
41,9611116
61,6611116

Optional accessories:

Optional Mounting Accessories for Emergency Lights

Product CodeProduct NameCompatible Product GroupsAdd to offer basket
TWTC1001Trail wall bracket TWTC1001

Information and offers on Trail Zone Lowbay emergency light TWTC271W