Zonespot II Midbay emergency light TWS9392WMT

Self-contained Escap Emergency light with 1 h Super Capacitor and Lumi Test Self-testing

The Zonespot II Midbay is a surface-mounted emergency light. The luminaire’s optics are designed to provide a broad, uniform light pattern that illuminates open areas effectively.
Thanks to the IP44 enclosure class, the Zonespot II is also suitable for damp areas. The luminaire is easy and quick to install thanks to a separate mounting base, which is also connected to the power supply.

1 h
icon-ce
EN 60598_2_22
icon-Escap
850 °C
43
icon-LED
icon-LumiTest
220-240 V 50/60 Hz AC
icon-ProtectionClassII
9005
icon-Through-wiring
Product codeTWS9392WMTElectrical number (FI)4148791
GTIN06438045028811TARIC code94056180
Weight0,90 kgMeasurements18,00 × 18,00 × 5,00 cm
Backup (h)YesBody materialplastic
CE MarkYesColourRAL9005
Electrical Installation2/3 x 2,5 mm²EN 60598-2-22Yes
EscapYesETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)850 IP ClassIP43
Light SourceLEDLumi TestYes
Luminous Flux (lm)75 Max Input Power VA3 VA
MountingSurfaceMounting optionPendel
Nominal Supply Voltage220-240 V, 50/60 Hz ACProtection ClassII
Temperature Range Min - Max (°C)-25...+35Suitable for Through-WiringYes
Product codeTWS9392WMT
Electrical number (FI)4148791
GTIN06438045028811
TARIC code94056180
Weight0,90 kg
Measurements18,00 × 18,00 × 5,00 cm
Backup (h)Yes
Body materialplastic
CE MarkYes
ColourRAL9005
Electrical Installation2/3 x 2,5 mm²
EN 60598-2-22Yes
EscapYes
ETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)850
IP ClassIP43
Light SourceLED
Lumi TestYes
Luminous Flux (lm)75
Max Input Power VA3 VA
MountingSurface
Mounting optionPendel
Nominal Supply Voltage220-240 V, 50/60 Hz AC
Protection ClassII
Temperature Range Min - Max (°C)-25...+35
Suitable for Through-WiringYes

Scale Images

Scale image

Light Distribution Charts

Emergency lighting for open areas (ceiling mounting)

  • 0.5 lux table for open areas, in accordance with EN 1838; 0.5-m border zone is taken into account in the table.
  • Level of measurement 0.02 m, measurement result in emergency mode
R1 distance from wall, X axis
R2 mounting distance, X axis
R3 mounting distance, Y axis
R4 distance from wall, Y axis

Emergency lighting for open areas (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R3 (m)R4 (m)
--0.5 lx0.5 lx0.5 lx0.5 lx
2.58.52442
3624.54.52
43.52552
61.53663
Emergency lighting for escape routes (ceiling mounting)

  • 1 lux table for the centre line of an escape route, in accordance with EN 1838.
  • Level of measurement 0.02 m, measurement results in emergency mode.
R1 distance from wall, X axis
R2 mounting distance, X axis
R4 distance from wall, Y axis

Emergency lighting for escape routes (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R4 (m)
--1 lx1 lx1 lx
2.58.5251
3625.51
43.5361
61.5371

Accessories

Product codeElectrical numberDescription
TW77507B4281135Shock protecting cover TW77507BAdd to cart
TWT92024244125Wall bracket TWT9202Add to cart