Products / Self Contained Systems / Emergency lights for open areas / Zonespot II: Lowbay / Zonespot II Lowbay emergency light Y9292WA
Zonespot II Lowbay emergency light Y9292WA
Self-contained Escap Emergency light with 1 h Super Capacitor and Wireless Central Monitoring (Invidually packed TWS9292WA)
The Zonespot II Lowbay is a surface-mounted emergency light that is particularly suitable for low spaces. The luminaire’s optics are designed to provide a broad, uniform light pattern that illuminates open areas effectively.
Thanks to the IP44 enclosure class, the Zonespot II is also suitable for damp areas. The luminaire is easy and quick to install thanks to a separate mounting base, which is also connected to the power supply.
Product code | Y9292WA | Electrical number (FI) | 4281540 | |
---|---|---|---|---|
GTIN | 6438045017013 | TARIC code | 94056180 | |
Weight | 1,00 kg | Measurements | 18,50 × 18,50 × 5,20 cm | |
Aalto Control | Yes | Backup (h) | Yes | |
Body material | plastic | CE Mark | Yes | |
Colour | RAL9003 (Signal white) | Electrical Installation | 2/3 x 2,5 mm² | |
EN 60598-2-22 | Yes | Escap | Yes | |
ETIM class | Emergency luminaire (EC001957) | Glow Wire Test of Plastic Materials (°C) | 850 | |
IP Class | IP43 | Light Source | LED | |
Lumi Test | Yes | Luminous Flux (lm) | 80 | |
Max Input Power VA | 3 VA | Mounting | Surface | |
Mounting option | Pendel | Nominal Supply Voltage | 220-240 V, 50/60 Hz AC | |
Protection Class | II | Temperature Range Min - Max (°C) | -25...+35 | |
Suitable for Through-Wiring | Yes |
Product code | Y9292WA |
---|---|
Electrical number (FI) | 4281540 |
GTIN | 6438045017013 |
TARIC code | 94056180 |
Weight | 1,00 kg |
Measurements | 18,50 × 18,50 × 5,20 cm |
Aalto Control | Yes |
Backup (h) | Yes |
Body material | plastic |
CE Mark | Yes |
Colour | RAL9003 (Signal white) |
Electrical Installation | 2/3 x 2,5 mm² |
EN 60598-2-22 | Yes |
Escap | Yes |
ETIM class | Emergency luminaire (EC001957) |
Glow Wire Test of Plastic Materials (°C) | 850 |
IP Class | IP43 |
Light Source | LED |
Lumi Test | Yes |
Luminous Flux (lm) | 80 |
Max Input Power VA | 3 VA |
Mounting | Surface |
Mounting option | Pendel |
Nominal Supply Voltage | 220-240 V, 50/60 Hz AC |
Protection Class | II |
Temperature Range Min - Max (°C) | -25...+35 |
Suitable for Through-Wiring | Yes |
Scale Images
Light Distribution Charts
- 0.5 lux table for open areas, in accordance with EN 1838; 0.5-m border zone is taken into account in the table.
- Level of measurement 0.02 m, measurement result in emergency mode
R1 distance from wall, X axis
R2 mounting distance, X axis
R3 mounting distance, Y axis
R4 distance from wall, Y axis
Emergency lighting for open areas (ceiling mounting)
Mounting height (m) | Below the light (lx) | R1 (m) | R2 (m) | R3 (m) | R4 (m) |
- | - | 0.5 lx | 0.5 lx | 0.5 lx | 0.5 lx |
2.5 | 2 | 4 | 8 | 8 | 4 |
3 | 1.6 | 4 | 8 | 8 | 4 |
4 | 1.4 | 3 | 8.5 | 8.5 | 3 |
- 1 lux table for the centre line of an escape route, in accordance with EN 1838.
- Level of measurement 0.02 m, measurement results in emergency mode.
R1 distance from wall, X axis
R2 mounting distance, X axis
R4 distance from wall, Y axis
Emergency lighting for escape routes (ceiling mounting)
Mounting height (m) | Below the light (lx) | R1 (m) | R2 (m) | R4 (m) |
- | - | 1 lx | 1 lx | 1 lx |
2.5 | 1.5 | 3 | 7 | 1 |
Downloads and Data sheets
File name | Download |
---|---|
Product card | Download |
General information about installing Teknoware lights | Download |
Installation Guide Line/Zonespot, Surface-installation - VOT79 | Download |
Accessories
Product code | Electrical number | Description | |
---|---|---|---|
TW77507B | 4281135 | Shock protecting cover TW77507B | Add to cart |
TWT9202 | 4244125 | Wall bracket TWT9202 | Add to cart |
How to contact our sales teams
Teknoware Emergency Lighting distributors and sales offices around the world: