Zonespot II Lowbay emergency light Y9271WT

24-230 V centrally supplied LED emergency light (Invidually packed TWT9271WT)

The Zonespot II Lowbay is a surface-mounted emergency light that is particularly suitable for low spaces. The luminaire’s optics are designed to provide a broad, uniform light pattern that illuminates open areas effectively.
Thanks to the IP44 enclosure class, the Zonespot II is also suitable for damp areas. The luminaire is easy and quick to install thanks to a separate mounting base, which is also connected to the power supply.

icon-ce
EN 60598_2_22
650 °C
43
icon-LED
24-230 V 50/60 Hz AC DC
icon-ProtectionClassIII
icon-ProtectionClassII
9005
icon-Through-wiring
Product codeY9271WTElectrical number (FI)4148905
GTIN06438045029979TARIC code94056080
Weight0,60 kgMeasurements18,50 × 18,50 × 5,20 cm
Body materialplasticCE MarkYes
ColourRAL9005 (Jet black)Electrical Installation2 x 2,5 mm² (24 V), 3 x 2,5 mm² (230 V)
EN 60598-2-22YesETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)650 IP ClassIP43
Light SourceLEDLuminous Flux (lm)255
Max Input Power VA8 VA (24 V), 10 VA (230 V)Max Input Power W5 W (24 V), 5 W (230 V)
MountingSurfaceMounting optionPendel
Nominal Supply Voltage24-230 V, 50/60 Hz AC, DCProtection ClassIII (24 V), II (230 V)
Temperature Range Min - Max (°C)-30...+50Suitable for Through-WiringYes
Product codeY9271WT
Electrical number (FI)4148905
GTIN06438045029979
TARIC code94056080
Weight0,60 kg
Measurements18,50 × 18,50 × 5,20 cm
Body materialplastic
CE MarkYes
ColourRAL9005 (Jet black)
Electrical Installation2 x 2,5 mm² (24 V), 3 x 2,5 mm² (230 V)
EN 60598-2-22Yes
ETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)650
IP ClassIP43
Light SourceLED
Luminous Flux (lm)255
Max Input Power VA8 VA (24 V), 10 VA (230 V)
Max Input Power W5 W (24 V), 5 W (230 V)
MountingSurface
Mounting optionPendel
Nominal Supply Voltage24-230 V, 50/60 Hz AC, DC
Protection ClassIII (24 V), II (230 V)
Temperature Range Min - Max (°C)-30...+50
Suitable for Through-WiringYes

Scale Images

Scale image

Light Distribution Charts

Emergency lighting for open areas (ceiling mounting)

  • 0.5 lux table for open areas, in accordance with EN 1838; 0.5-m border zone is taken into account in the table.
  • Level of measurement 0.02 m, measurement result in emergency mode
R1 distance from wall, X axis
R2 mounting distance, X axis
R3 mounting distance, Y axis
R4 distance from wall, Y axis

Emergency lighting for open areas (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R3 (m)R4 (m)
--0.5 lx0.5 lx0.5 lx0.5 lx
2.54.35.510105.5
41.9611116
61.6611116
Emergency lighting for escape routes (ceiling mounting)

  • 1 lux table for the centre line of an escape route, in accordance with EN 1838.
  • Level of measurement 0.02 m, measurement results in emergency mode.
R1 distance from wall, X axis
R2 mounting distance, X axis
R4 distance from wall, Y axis

Emergency lighting for escape routes (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R4 (m)
--1 lx1 lx1 lx
2.54.35111
41.74141

How to contact our sales teams