Addressable 24 V centrally supplied LED emergency light

The Zonespot II Lowbay is a surface-mounted emergency light that is particularly suitable for low spaces. The luminaire’s optics are designed to provide a broad, uniform light pattern that illuminates open areas effectively.
Thanks to the IP44 enclosure class, the Zonespot II is also suitable for damp areas. The luminaire is easy and quick to install thanks to a separate mounting base, which is also connected to the power supply.

icon-ce
EN 1838
EN 60598_2_22
650 °C
43
icon-LED
24 V 50/60 Hz AC DC
icon-ProtectionClassIII
9005
icon-TapsaControl
icon-Through-wiring
Product codeTWT9241WKTElectrical number (FI)4148807
GTIN06438045028972TARIC code94056180
Weight0,50 kgMeasurements18,00 × 18,00 × 5,00 cm
Body materialplasticCE MarkYes
ColourRAL9005Electrical Installation2/3 x 2,5 mm²
EN 1838YesEN 60598-2-22Yes
ETIM classEmergency luminaire (EC001957)Glow Wire Test of Plastic Materials (°C)650
IP ClassIP43Light SourceLED
Luminous Flux (lm)255 Max Input Power VA3,1 VA
Max Input Power W3,1 WMountingSurface
Mounting optionPendelNominal Supply Voltage24 V, 50/60 Hz AC, DC
Protection ClassIIITapsa ControlYes
Temperature Range Min - Max (°C)-30...+50Suitable for Through-WiringYes
Product codeTWT9241WKT
Electrical number (FI)4148807
GTIN06438045028972
TARIC code94056180
Weight0,50 kg
Measurements18,00 × 18,00 × 5,00 cm
Body materialplastic
CE MarkYes
ColourRAL9005
Electrical Installation2/3 x 2,5 mm²
EN 1838Yes
EN 60598-2-22Yes
ETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)650
IP ClassIP43
Light SourceLED
Luminous Flux (lm)255
Max Input Power VA3,1 VA
Max Input Power W3,1 W
MountingSurface
Mounting optionPendel
Nominal Supply Voltage24 V, 50/60 Hz AC, DC
Protection ClassIII
Tapsa ControlYes
Temperature Range Min - Max (°C)-30...+50
Suitable for Through-WiringYes

Scale Images

Scale image

Light Distribution Charts

Emergency lighting for open areas (ceiling mounting)

  • 0.5 lux table for open areas, in accordance with EN 1838; 0.5-m border zone is taken into account in the table.
  • Level of measurement 0.02 m, measurement result in emergency mode
R1 distance from wall, X axis
R2 mounting distance, X axis
R3 mounting distance, Y axis
R4 distance from wall, Y axis

Emergency lighting for open areas (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R3 (m)R4 (m)
--0.5 lx0.5 lx0.5 lx0.5 lx
2.54.35.510105.5
41.9611116
61.6611116
Emergency lighting for escape routes (ceiling mounting)

  • 1 lux table for the centre line of an escape route, in accordance with EN 1838.
  • Level of measurement 0.02 m, measurement results in emergency mode.
R1 distance from wall, X axis
R2 mounting distance, X axis
R4 distance from wall, Y axis

Emergency lighting for escape routes (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R4 (m)
--1 lx1 lx1 lx
2.54.35111
41.74141