Zonespot II Lowbay emergency light TWS0492WM4

Self-contained ESCAP Emergency Light with 1 h Super Capacitor and Lumi Test Self-testing

The Zonespot II Lowbay is a small and elegant emergency light, for recess mounting. It is specially designed for illuminating open areas. Zonespot II Lowbay takes advantage of the latest LED technology.

1 h
icon-ce
EN 1838
EN 60598_2_22
icon-Escap
850 °C
20
icon-LED
icon-LumiTest
220-240 V 50/60 Hz AC
icon-ProtectionClassI
9003
icon-Through-wiring
Product codeTWS0492WM4Electrical number (FI)4244112
GTIN6438045024370TARIC code94056180
Weight0,80 kgMeasurements10,00 × 10,00 × 5,00 cm
Backup (h)1 hBody materialplastic
CE MarkYesColourRAL9003 (Signal white)
Electrical Installation3 x 2,5 mm²EN 1838Yes
EN 60598-2-22YesEscapYes
ETIM classEmergency luminaire (EC001957)Glow Wire Test of Plastic Materials (°C)850
IP ClassIP20Light SourceLED
Lumi TestYesLuminous Flux (lm)80
Max Input Power VA3 VAMountingRecess
Nominal Supply Voltage220-240 V, 50/60 Hz ACProtection ClassI
Aperture for Recess Mountingø75Temperature Range Min - Max (°C)-25...+35
Suitable for Through-WiringYes
Product codeTWS0492WM4
Electrical number (FI)4244112
GTIN6438045024370
TARIC code94056180
Weight0,80 kg
Measurements10,00 × 10,00 × 5,00 cm
Backup (h)1 h
Body materialplastic
CE MarkYes
ColourRAL9003 (Signal white)
Electrical Installation3 x 2,5 mm²
EN 1838Yes
EN 60598-2-22Yes
EscapYes
ETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)850
IP ClassIP20
Light SourceLED
Lumi TestYes
Luminous Flux (lm)80
Max Input Power VA3 VA
MountingRecess
Nominal Supply Voltage220-240 V, 50/60 Hz AC
Protection ClassI
Aperture for Recess Mountingø75
Temperature Range Min - Max (°C)-25...+35
Suitable for Through-WiringYes

Scale Images

Scale image

Light Distribution Charts

Emergency lighting for open areas (ceiling mounting)

  • 0.5 lux table for open areas, in accordance with EN 1838; 0.5-m border zone is taken into account in the table.
  • Level of measurement 0.02 m, measurement result in emergency mode
R1 distance from wall, X axis
R2 mounting distance, X axis
R3 mounting distance, Y axis
R4 distance from wall, Y axis

Emergency lighting for open areas (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R3 (m)R4 (m)
--0.5 lx0.5 lx0.5 lx0.5 lx
2.524884
31.64884
41.438.58.53
Emergency lighting for escape routes (ceiling mounting)

  • 1 lux table for the centre line of an escape route, in accordance with EN 1838.
  • Level of measurement 0.02 m, measurement results in emergency mode.
R1 distance from wall, X axis
R2 mounting distance, X axis
R4 distance from wall, Y axis

Emergency lighting for escape routes (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R4 (m)
--1 lx1 lx1 lx
2.51.5371

Accessories

Product codeElectrical numberDescription 
TMT3894280929Gasket ring TMT389Add to cart

How to contact our sales teams

Teknoware Emergency Lighting distributors and sales offices around the world: