Trail Line Midbay emergency light TWTC471W

24-230 V centrally supplied emergency light

Teknoware Trail is an elegant emergency light that is easy to install on a lighting track. Thanks to its unique design, it is suitable for direct mounting on common lighting track systems. The luminaire can also be mounted directly on the ceiling. Trail has a modern and streamlined appearance so it blends in with the surroundings and architecture. Trail’s wide product family and range of optics offer many options to suit a variety of applications and systems.
Trail Line Midbay provides a long and narrow pattern that illuminates the escape routes efficiently.

icon-ce
EN 1838
EN 60598_2_22
650 °C
20
icon-LED
24-230 V 50/60 Hz AC DC
icon-ProtectionClassIII
icon-ProtectionClassI
9003
icon-Through-wiring
Product codeTWTC471WElectrical number (FI)4244191
GTIN6438045025162TARIC code94056180
Weight0,90 kgMeasurements34,50 × 8,00 × 4,80 cm
Body materialmetalCE MarkYes
ColourRAL9003 (Signal white)Electrical Installation2 x 2,5 mm² (24 V), 3 x 2,5 mm² (230 V)
EN 1838YesEN 60598-2-22Yes
ETIM classEmergency luminaire (EC001957)Glow Wire Test of Plastic Materials (°C)650
IP ClassIP20Light SourceLED
Luminous Flux (lm)240 Max Input Power VA7,5 VA (24 V), 11 VA (230 V)
Max Input Power W4 W (24 V), 4 W (230 V)MountingCeiling, Rail, Surface
Nominal Supply Voltage24-230 V, 50/60 Hz AC, DCProtection ClassIII (24 V), I (230 V)
Temperature Range Min - Max (°C)-30...+50Suitable for Through-WiringYes
Product codeTWTC471W
Electrical number (FI)4244191
GTIN6438045025162
TARIC code94056180
Weight0,90 kg
Measurements34,50 × 8,00 × 4,80 cm
Body materialmetal
CE MarkYes
ColourRAL9003 (Signal white)
Electrical Installation2 x 2,5 mm² (24 V), 3 x 2,5 mm² (230 V)
EN 1838Yes
EN 60598-2-22Yes
ETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)650
IP ClassIP20
Light SourceLED
Luminous Flux (lm)240
Max Input Power VA7,5 VA (24 V), 11 VA (230 V)
Max Input Power W4 W (24 V), 4 W (230 V)
MountingCeiling, Rail, Surface
Nominal Supply Voltage24-230 V, 50/60 Hz AC, DC
Protection ClassIII (24 V), I (230 V)
Temperature Range Min - Max (°C)-30...+50
Suitable for Through-WiringYes

Scale Images

Scale image

Light Distribution Charts

Emergency lighting for escape routes (ceiling mounting)

  • 1 lux table for the centre line of an escape route, in accordance with EN 1838.
  • Level of measurement 0.02 m, measurement results in emergency mode.
R1 distance from wall, X axis
R2 mounting distance, X axis
R4 distance from wall, Y axis

Emergency lighting for escape routes (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R4 (m)
--1 lx1 lx1 lx
2.5405111
4156.5171
667.5201
83.57211
1026.5211

Required products

Product codeElectrical numberDescription 
TWTC10004148665Lighting track adapter TWTC1000 for Trail emergency lightsAdd to cart

Compatible products

Product codeElectrical numberDescription 
TWTC10014148629Trail wall bracket TWTC1001Add to cart

Accessories

Product codeElectrical numberDescription 
TWTC10014148629Trail wall bracket TWTC1001Add to cart

How to contact our sales teams

Teknoware Emergency Lighting distributors and sales offices around the world: