Tapsa Control Central Battery Unit TKT6508CP

Central battery system in TKT65xxCX series, as all our Tapsa Control central battery systems, takes care of the testing automatically.
Suitable for medium sized and large buildings.
Technical data:

  • input voltage 230 VAC
  • output voltage under normal conditions 230 VAC
  • output voltage in battery mode 216 VDC
  • battery voltage of 216 V is generated by 18 pieces of 12 V batteries connected in series
  • 8, 16 or 24 output circuits
  • max 16 luminaires per circuit
icon-ce
EN 50171
icon-IntelligentControl
34
1~ N/PE 220-240 VAC 50 Hz
9003
icon-TapsaControl
Product codeTKT6508CPElectrical number (FI)7123923
GTIN6438045018379TARIC code85044095
Weight49,50 kgMeasurements27,60 × 60,60 × 78,10 cm
Battery Voltage (VDC)216Body materialsheet metal
CE MarkYesColourRAL9003 (Signal white)
EN 50171YesETIM classEmergency lighting power supply unit (EC002678)
Intelligent ControllerYesIP ClassIP34
Max Battery Capacity (Ah)65Max Load Inrush Current per Single Output Circuit / 1 ms (A)120
Max Total Load, 1 h Duration (W)2000 WMax total load, battery operation 1 h (W)2000 W
Max total load, battery operation 3 h (W)2000 WMax total load, mains operation (VA)2000
Nominal Supply Voltage1~ N/PE 220-240 VAC, 50 HzNumber of Output Circuits8 x 250 VA / W
Output Voltage, Battery Supply (VDC)216Nominal Output Voltage, Mains Supply (VAC)220-240 VAC
Power Consumption (VA)3100 Required Short Circuit Current per Single Output Circuit (A)7
Tapsa ControlYes
Product codeTKT6508CP
Electrical number (FI)7123923
GTIN6438045018379
TARIC code85044095
Weight49,50 kg
Measurements27,60 × 60,60 × 78,10 cm
Battery Voltage (VDC)216
Body materialsheet metal
CE MarkYes
ColourRAL9003 (Signal white)
EN 50171Yes
ETIM classEmergency lighting power supply unit (EC002678)
Intelligent ControllerYes
IP ClassIP34
Max Battery Capacity (Ah)65
Max Load Inrush Current per Single Output Circuit / 1 ms (A)120
Max Total Load, 1 h Duration (W)2000 W
Max total load, battery operation 1 h (W)2000 W
Max total load, battery operation 3 h (W)2000 W
Max total load, mains operation (VA)2000
Nominal Supply Voltage1~ N/PE 220-240 VAC, 50 Hz
Number of Output Circuits8 x 250 VA / W
Output Voltage, Battery Supply (VDC)216
Nominal Output Voltage, Mains Supply (VAC)220-240 VAC
Power Consumption (VA)3100
Required Short Circuit Current per Single Output Circuit (A)7
Tapsa ControlYes

Required products

Product codeElectrical numberDescription 
TST65017118905BACnet Interface TST6501Add to cart
TST65217118914ACM Interface TST6521Add to cart
TST65247118918WebCM Interface TST6524Add to cart

Product codeElectrical numberDescription 
TST51317123927ACM PC Software TST5131Add to cart

How to contact our sales teams

Teknoware Emergency Lighting distributors and sales offices around the world: