Solid Line Midbay emergency light TWT4341WK

Addressable 24 V centrally supplied emergency light for escape routes

Solid Line Midbay is developed for escape route emergency lighting.
High enclosure class (IP65) ensures that the luminaire is completely dust proof and water proof.
Solid is suitable for example for industrial premises and parking halls. Escap and centrally supplied luminaires are also suitable for outdoor use. The Solid luminaire uses long lasting leds as its light source.
Special attention has been paid to the design, for easy installation.

icon-ce
EN 1838
EN 60598_2_22
650 °C
65
icon-LED
24 V 50/60 Hz AC DC
icon-ProtectionClassIII
9003 (Signal white)
icon-TapsaControl
icon-Through-wiring
Product codeTWT4341WKElectrical number (FI)4226367
GTIN6438045023915TARIC code94056180
Weight1,10 kgMeasurements37,10 × 18,10 × 5,70 cm
Body materialplasticCE MarkYes
ColourRAL9003 (Signal white)Electrical Installation2/3 x 2,5 mm²
EN 1838YesEN 60598-2-22Yes
Glow Wire Test of Plastic Materials (°C)650 IP ClassIP65
Light SourceLEDLuminous Flux (lm)300
Max Input Power VA3,4 VAMax Input Power W3,4 W
MountingSurfaceNominal Supply Voltage24 V, 50/60 Hz AC, DC
Protection ClassIIITapsa ControlYes
Temperature Range Min - Max (°C)-30…+50Suitable for Through-WiringYes
Product codeTWT4341WK
Electrical number (FI)4226367
GTIN6438045023915
TARIC code94056180
Weight1,10 kg
Measurements37,10 × 18,10 × 5,70 cm
Body materialplastic
CE MarkYes
ColourRAL9003 (Signal white)
Electrical Installation2/3 x 2,5 mm²
EN 1838Yes
EN 60598-2-22Yes
Glow Wire Test of Plastic Materials (°C)650
IP ClassIP65
Light SourceLED
Luminous Flux (lm)300
Max Input Power VA3,4 VA
Max Input Power W3,4 W
MountingSurface
Nominal Supply Voltage24 V, 50/60 Hz AC, DC
Protection ClassIII
Tapsa ControlYes
Temperature Range Min - Max (°C)-30…+50
Suitable for Through-WiringYes

Light Distribution Charts

Emergency lighting for escape routes (ceiling mounting)

  • 1 lux table for the centre line of an escape route, in accordance with EN 1838.
  • Level of measurement 0.02 m, measurement results in emergency mode.
R1 distance from wall, X axis
R2 mounting distance, X axis
R4 distance from wall, Y axis

Emergency lighting for escape routes (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R4 (m)
--1 lx1 lx1 lx
2.5575121
3395.5141
4226161
69.57201
858201
1039211
122.59211

Accessories

Product codeElectrical numberDescription
TWT30014226329Solid Recess Mounting Frame TWT3001Add to cart
TWT30074148679Solid lid TWT3007Add to cart
TWT30064148553Solid Suspension Bracket TWT3006Add to cart
TWT30044226332Solid Ceiling bracket TWT3004Add to cart
TWT30034226331Solid Flag bracket TWT3003Add to cart
TWT30024226330Solid Wall bracket TWT3002Add to cart

How to contact our sales teams

Teknoware Emergency Lighting distributors and sales offices around the world: