Robust 86 Emergency Light TWT8651WK

Addressable 230 V centrally supplied Emergency Light

Robust 86 is a emergency light for surface mounting to the ceiling. It has an especially robust design and a metal body.
With their high IP class and a very rugged construction, the luminaires are suitable for demanding environments, such as damp locations, industry and tunnels.

icon-ce
EN 60598_2_22
650 °C
67
icon-LED
220-240 V 50/60 Hz AC DC
icon-ProtectionClassI
icon-TapsaControl
icon-Through-wiring
Product codeTWT8651WKElectrical number (FI)4282383
GTIN6438045023045TARIC code94056180
Weight1,30 kgMeasurements30,40 × 12,60 × 12,60 cm
Body materialmetalCE MarkYes
Electrical Installation3 x 2,5 mm²EN 60598-2-22Yes
ETIM classEmergency luminaire (EC001957)Glow Wire Test of Plastic Materials (°C)650
IP ClassIP67Light SourceLED
Luminous Flux (lm)900 Max Input Power VA40 VA
Max Input Power W18 WNominal Supply Voltage220-240 V, 50/60 Hz AC, DC
Protection ClassITapsa ControlYes
Temperature Range Min - Max (°C)-30…+50Suitable for Through-WiringYes
Product codeTWT8651WK
Electrical number (FI)4282383
GTIN6438045023045
TARIC code94056180
Weight1,30 kg
Measurements30,40 × 12,60 × 12,60 cm
Body materialmetal
CE MarkYes
Electrical Installation3 x 2,5 mm²
EN 60598-2-22Yes
ETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)650
IP ClassIP67
Light SourceLED
Luminous Flux (lm)900
Max Input Power VA40 VA
Max Input Power W18 W
Nominal Supply Voltage220-240 V, 50/60 Hz AC, DC
Protection ClassI
Tapsa ControlYes
Temperature Range Min - Max (°C)-30…+50
Suitable for Through-WiringYes

Scale Images

Scale image

Light Distribution Charts

Emergency lighting for open areas (ceiling mounting)

  • 0.5 lux table for open areas, in accordance with EN 1838; 0.5-m border zone is taken into account in the table.
  • Level of measurement 0.02 m, measurement result in emergency mode
R1 distance from wall, X axis
R2 mounting distance, X axis
R3 mounting distance, Y axis
R4 distance from wall, Y axis

Emergency lighting for open areas (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R3 (m)R4 (m)
--0.5 lx0.5 lx0.5 lx0.5 lx
43210.214147.5
61411.716168.5
8813.216168.5
10513.216168.5
12313.216168.5
142.513.216168.5
1621014147
181.5812126
2017885
Emergency lighting for escape routes (ceiling mounting)

  • 1 lux table for the centre line of an escape route, in accordance with EN 1838.
  • Level of measurement 0.02 m, measurement results in emergency mode.
R1 distance from wall, X axis
R2 mounting distance, X axis
R4 distance from wall, Y axis

Emergency lighting for escape routes (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R4 (m)
--1 lx1 lx1 lx
4328181
6149221
889241
1059241