Linespot II Lowbay emergency light TWT9951WKT

Addressable 230 V centrally supplied LED Emergency Light

The Linespot II Lowbay is a surface-mounted emergency light that is particularly suitable for low spaces. The luminaire’s optics are designed to provide a long and narrow light pattern that illuminates corridors and escape routes efficiently.
Thanks to the IP44 enclosure class, the Linespot II is also suitable for damp areas. The luminaire is easy and fast to install, thanks to a separate mounting base, which is also connected to the power supply.

icon-ce
EN 60598_2_22
650 °C
icon-IntelligentControl
43
icon-LED
220-240 V 50/60 Hz AC DC
icon-ProtectionClassII
9005 (Jet black)
icon-TapsaControl
icon-Through-wiring
Product codeTWT9951WKTElectrical number (FI)4148823
GTIN06438045029139TARIC code94056180
Weight0,50 kgMeasurements18,00 × 18,00 × 5,00 cm
Body materialplasticCE MarkYes
ColourRAL9005 (Jet black)Electrical Installation2/3 x 2,5 mm²
EN 60598-2-22YesETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)650 Intelligent ControllerYes
IP ClassIP43Light SourceLED
Luminous Flux (lm)230 Max Input Power VA10 VA
Max Input Power W5,5 WMountingSurface
Mounting optionPendelNominal Supply Voltage220-240 V, 50/60 Hz AC, DC
Protection ClassIITapsa ControlYes
Temperature Range Min - Max (°C)-30...+50Suitable for Through-WiringYes
Product codeTWT9951WKT
Electrical number (FI)4148823
GTIN06438045029139
TARIC code94056180
Weight0,50 kg
Measurements18,00 × 18,00 × 5,00 cm
Body materialplastic
CE MarkYes
ColourRAL9005 (Jet black)
Electrical Installation2/3 x 2,5 mm²
EN 60598-2-22Yes
ETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)650
Intelligent ControllerYes
IP ClassIP43
Light SourceLED
Luminous Flux (lm)230
Max Input Power VA10 VA
Max Input Power W5,5 W
MountingSurface
Mounting optionPendel
Nominal Supply Voltage220-240 V, 50/60 Hz AC, DC
Protection ClassII
Tapsa ControlYes
Temperature Range Min - Max (°C)-30...+50
Suitable for Through-WiringYes

Scale Images

Scale image

Light Distribution Charts

Emergency lighting for escape routes (ceiling mounting)

  • 1 lux table for the centre line of an escape route, in accordance with EN 1838.
  • Level of measurement 0.02 m, measurement results in emergency mode.
R1 distance from wall, X axis
R2 mounting distance, X axis
R4 distance from wall, Y axis

Emergency lighting for escape routes (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R4 (m)
--1 lx1 lx1 lx
2.57.59211
4310281
61.59221

Accessories

Product codeElectrical numberDescription
TW77507B4281135Shock protecting cover TW77507BAdd to cart
TWT92024244125Wall bracket TWT9202Add to cart

How to contact our sales teams

Teknoware Emergency Lighting distributors and sales offices around the world: