Central Battery Unit TKT6512BP

TKT65B series central battery system offers an effective solution to supply medium to high number of emergency and exit lights. It is suitable for medium sized buildings.
The new TKT65xxBP models are equipped with a door and their enclosure class is IP34.
Technical data:

  • input voltage 230 VAC
  • output voltage under normal conditions 230 VAC
  • output voltage in battery mode 216 VDC
  • battery voltage of 216 V is generated by 18 pieces of 12 V batteries connected in series
  • 6, 12, 18 or 24 output circuits
icon-ce
EN 50171
34
1~ N/PE 220-240 VAC 50 Hz
9003
Product codeTKT6512BPElectrical number (FI)7123933
GTIN6438045019888TARIC code85044095
Weight30,00 kgMeasurements59,00 × 26,20 × 86,20 cm
Battery Voltage (VDC)216Body materialsheet metal
CE MarkYesColourRAL9003 (Signal white)
EN 50171YesETIM classEmergency lighting power supply unit (EC002678)
IP ClassIP34Max Battery Capacity (Ah)65
Max Load Inrush Current per Single Output Circuit / 1 ms (A)120 Max Total Load, 1 h Duration (W)3000 W
Max total load, battery operation 1 h (W)3000 WMax total load, battery operation 3 h (W)3000 W
Max total load, mains operation (VA)2580 Nominal Supply Voltage1~ N/PE 220-240 VAC, 50 Hz
Number of Output Circuits12 x 250 VA / WOutput Voltage, Battery Supply (VDC)216
Nominal Output Voltage, Mains Supply (VAC)220-240 VACPower Consumption (VA)3680
Required Short Circuit Current per Single Output Circuit (A)11
Product codeTKT6512BP
Electrical number (FI)7123933
GTIN6438045019888
TARIC code85044095
Weight30,00 kg
Measurements59,00 × 26,20 × 86,20 cm
Battery Voltage (VDC)216
Body materialsheet metal
CE MarkYes
ColourRAL9003 (Signal white)
EN 50171Yes
ETIM classEmergency lighting power supply unit (EC002678)
IP ClassIP34
Max Battery Capacity (Ah)65
Max Load Inrush Current per Single Output Circuit / 1 ms (A)120
Max Total Load, 1 h Duration (W)3000 W
Max total load, battery operation 1 h (W)3000 W
Max total load, battery operation 3 h (W)3000 W
Max total load, mains operation (VA)2580
Nominal Supply Voltage1~ N/PE 220-240 VAC, 50 Hz
Number of Output Circuits12 x 250 VA / W
Output Voltage, Battery Supply (VDC)216
Nominal Output Voltage, Mains Supply (VAC)220-240 VAC
Power Consumption (VA)3680
Required Short Circuit Current per Single Output Circuit (A)11

Required products

Product codeElectrical numberDescriptionMeasurements 
TEA0247123870Batterie 65 Ah / 12 V 35,00 × 16,90 × 18,00 cmAdd to cart
TEA0227123868Batterie 24 Ah / 12 V 16,70 × 17,70 × 12,60 cmAdd to cart
TEA0237123869Batterie 38 Ah / 12 V 19,90 × 16,70 × 17,20 cmAdd to cart
TEA0207123866Batterie 6,5 Ah / 12 V15,10 × 6,50 × 10,20 cmAdd to cart
TEA0217123867Batterie 17 Ah / 12 V 18,30 × 7,90 × 16,90 cmAdd to cart

Product codeElectrical numberDescriptionIP Class 
TK6500B7118820Battery Cabinet for Batteries, space for batteries 18 x12 V / 15 AhIP20Add to cart
TKT6500P7123919Battery Cabinet for Batteries, space for batteries 6 x12 V / 100 AhIP34Add to cart
TK6500BP7123918Battery Cabinet for Batteries, space for batteries 18 x12 V / 15 AhIP34Add to cart
TKT65007118821Battery Cabinet for Batteries, space for batteries 6x12 V / 100AhIP20Add to cart

Product codeElectrical numberDescription 
XJ997E7118823Battery cable for three TKT6500 Battery Cabinets, TKT65- and TKT66 Central Battery SystemsAdd to cart
XJ997C7118896Battery cables for two Battery Cabinets, TKT65- and TKT66 Central Battery SystemsAdd to cart
XJ997B7118852Battery cable for 6,5 Ah batteries, TKT65- and TKT66 Central Battery SystemsAdd to cart
XJ9977118853Battery cable for ≥15 Ah batteries, TKT65- and TKT66 Central Battery SystemsAdd to cart

How to contact our sales teams

Teknoware Emergency Lighting distributors and sales offices around the world: