Safe 6 LED Emergency Light Y0651WK

220-240 V 50/60 Hz AC, DC
LED
IP 44
RAL 9003
650 °C
EN 60598-2-22

230 V centrally supplied LED emergency light (Invidually packed TWT0651WK)

SAFE 6 is Teknoware's LED emergency light for areas with 2,5-10 meters high ceilings. The plastic bodied emergency light can be ceiling, wall and flag mounted.

SAFE 6 is splash proof, so the luminaires are suitable for damp locations, for example for parking hall and outdoor roofed shelters.

SAFE 6 emergency light is suitable for open areas. It also works as emergency light for escape routes with a separate lens set.

Product CodeY0651WK
FeatureIntelligent Controller, Tapsa Control
Mounting (standard)ceiling, wall, flag
Mounting (optional)pendel, recess
Customs Code94056080
GTIN Code6438045017662
ETIM Product ClassEC001957
Length267 mm
Width153 mm
Height70 mm
Weight1,0 kg
Max Input Power VA13 VA
Max Input Power W7,5 W
Nominal Supply Voltage220-240 V, 50/60 Hz AC, DC
Protection ClassI
IP ClassIP44
Temperature Range Min - Max-30...+50 °C
Glow Wire Test of Plastic Materials650 °C
Light SourceLED
Body Materialplastic
Aperture for Recess Mounting270 x 60 mm
ColourRAL9003
Electrical Installation3 x 2,5 mm²
Luminous Flux345 lm

Emergency lighting for escape routes (ceiling mounting)

  • Table of 1 lux for escape routes in the middle line according to the norm EN 1838.
  • Level of measurement 0,02 m, measurement result with battery operation.
Y R1 R4 R2 X h
  • R1 distance from wall (X axis)
  • R2 installation distance between lights (X axis)
  • R4 distance from wall (Y axis)

Y0651WK

Mounting height (m)Below the light luxR1 (m)R2 (m)R4 (m)
1 lux1 lux1 lux
2,5184,7113,9
475135,2
63,14,8144,8
81,72,5132,1

Emergency lighting for open areas (ceiling mounting)

  • Table of 0,5 lux for open areas according to the norm EN 1838, 0,5 m edge district is considered in the table.
  • Level of measurement 0,02 m, measurement result with battery operation.
Y R1 R3 R2 X h R4
  • R1 distance from wall (X axis)
  • R2 installation distance between lights (X axis)
  • R3 installation distance between lights (Y axis)
  • R4 distance from wall (Y axis)

Y0651WK

Mounting height (m)Below the light luxR1 (m)R2 (m)R3 (m)R4 (m)
0,5 lux0,5 lux0,5 lux0,5 lux
2,5186,2664,6
477,4886,6
63,17,610107,5
81,77,610107,5

Optional accessories:

Shock Protecting Covers for Emergency Lights

Product CodeProduct NameCompatible Product GroupsAdd to offer basket
TW77508BShock protecting cover TW77508BESC 0,5 Emergency Exit Lights, ESC 4 Emergency Exit Lights, ESC 90 Emergency Exit Lights, Safe 82 Emergency Lights

Optional Mounting Accessories for Emergency Lights

Product CodeProduct NameCompatible Product GroupsAdd to offer basket
TW77504CSuspension bracket TW77504CESC 4 Emergency Exit Lights, Safe 6 Emergency Lights
TW77504DSuspension bracket TW77504DESC 4 Emergency Exit Lights, Safe 6 Emergency Lights
TWT6001BRecess mounting frame TWT6001BSafe 6 Emergency Lights, ESC 6

Other Accessories for Emergency Lights

Product CodeProduct NameCompatible Product GroupsAdd to offer basket
XWT0655Lens set XWT0655Safe 6 Emergency Lights

You may also be interested in these products:

Addressable 230 V Centrally Supplied Emergency Exit Lights

Product CodeNominal Supply VoltagePictogramPictogram InfoAdd to offer basket
TWT9051WK220-240 V, 50/60 Hz AC, DC2-sided, 25 m
TWT8051WK220-240 V, 50/60 Hz AC, DC2-sided, 20/26/30 m

Information and offers on Safe 6 LED Emergency Light Y0651WK