Trail Zone Midbay emergency light TWSC592WM
Self-contained Escap Emergency light with 1 h super capacitor and Lumi Test self-testing
Teknoware Trail is an elegant emergency light that is easy to install on a lighting track. Thanks to its unique design, it is suitable for direct mounting on common lighting track systems. The luminaire can also be mounted directly on the ceiling. Trail has a modern and streamlined appearance so it blends in with the surroundings and architecture. Trail’s wide product family and range of optics offer many options to suit a variety of applications and systems.
Trail Zone Midbay provides a broad, even pattern that illuminates open areas efficiently.
Product code | TWSC592WM | Electrical number (FI) | 4148519 | |
---|---|---|---|---|
GTIN | 6438045025445 | TARIC code | 94056180 | |
Weight | 1,60 kg | Measurements | 46,50 × 8,00 × 4,80 cm | |
Backup (h) | Yes | Body material | metal | |
CE Mark | Yes | Colour | RAL9003 (Signal white) | |
Electrical Installation | 3 x 2,5 mm² | EN 1838 | Yes | |
EN 60598-2-22 | Yes | Escap | Yes | |
ETIM class | Emergency luminaire (EC001957) | Glow Wire Test of Plastic Materials (°C) | 850 | |
IP Class | IP20 | Light Source | LED | |
Lumi Test | Yes | Luminous Flux (lm) | 75 | |
Max Input Power VA | 3 VA | Mounting | Ceiling, Rail, Surface | |
Nominal Supply Voltage | 220-240 V, 50/60 Hz AC | Protection Class | I | |
Temperature Range Min - Max (°C) | -25...+35 | Suitable for Through-Wiring | Yes |
Product code | TWSC592WM |
---|---|
Electrical number (FI) | 4148519 |
GTIN | 6438045025445 |
TARIC code | 94056180 |
Weight | 1,60 kg |
Measurements | 46,50 × 8,00 × 4,80 cm |
Backup (h) | Yes |
Body material | metal |
CE Mark | Yes |
Colour | RAL9003 (Signal white) |
Electrical Installation | 3 x 2,5 mm² |
EN 1838 | Yes |
EN 60598-2-22 | Yes |
Escap | Yes |
ETIM class | Emergency luminaire (EC001957) |
Glow Wire Test of Plastic Materials (°C) | 850 |
IP Class | IP20 |
Light Source | LED |
Lumi Test | Yes |
Luminous Flux (lm) | 75 |
Max Input Power VA | 3 VA |
Mounting | Ceiling, Rail, Surface |
Nominal Supply Voltage | 220-240 V, 50/60 Hz AC |
Protection Class | I |
Temperature Range Min - Max (°C) | -25...+35 |
Suitable for Through-Wiring | Yes |
Scale Images
Light Distribution Charts
- 0.5 lux table for open areas, in accordance with EN 1838; 0.5-m border zone is taken into account in the table.
- Level of measurement 0.02 m, measurement result in emergency mode
Emergency lighting for open areas (ceiling mounting)
Mounting height (m) | Below the light (lx) | R1 (m) | R2 (m) | R3 (m) | R4 (m) |
- | - | 0.5 lx | 0.5 lx | 0.5 lx | 0.5 lx |
2.5 | 8.5 | 2 | 4 | 4 | 2 |
3 | 6 | 2 | 4.5 | 4.5 | 2 |
4 | 3.5 | 2 | 5 | 5 | 2 |
6 | 1.5 | 3 | 6 | 6 | 3 |
- 1 lux table for the centre line of an escape route, in accordance with EN 1838.
- Level of measurement 0.02 m, measurement results in emergency mode.
Emergency lighting for escape routes (ceiling mounting)
Mounting height (m) | Below the light (lx) | R1 (m) | R2 (m) | R4 (m) |
- | - | 1 lx | 1 lx | 1 lx |
2.5 | 8.5 | 2 | 5 | 1 |
3 | 6 | 2 | 5.5 | 1 |
4 | 3.5 | 3 | 6 | 1 |
6 | 1.5 | 3 | 7 | 1 |
Downloads and Data sheets
File name | Download |
---|---|
Product card | Download |
General information about installing Teknoware lights | Download |
Installation Guide Trail - VOT116 | Download |
Required products
Product code | Electrical number | Description | |
---|---|---|---|
TWTC1000 | 4148665 | Lighting track adapter TWTC1000 for Trail emergency lights | Add to cart |
Compatible products
Product code | Electrical number | Description | |
---|---|---|---|
TWTC1002 | 4148630 | Trail wall bracket TWTC1002 | Add to cart |
Accessories
Product code | Electrical number | Description | |
---|---|---|---|
TWTC1002 | 4148630 | Trail wall bracket TWTC1002 | Add to cart |
How to contact our sales teams
Teknoware Emergency Lighting distributors and sales offices around the world: