Linespot II Midbay emergency light TWS8892WA

Self-contained Escap Emergency light with 1 h Super Capacitor and Wireless Central Monitoring

The Linespot II Midbay is a surface-mounted emergency light. The luminaire’s optics are designed to provide a long and narrow light pattern that illuminates corridors and escape routes efficiently.
Thanks to the IP44 enclosure class, the Linespot II is also suitable for damp areas. The luminaire is easy and fast to install, thanks to a separate mounting base, which is also connected to the power supply.

icon-AaltoControl
1 h
icon-ce
EN 60598_2_22
icon-Escap
850 °C
43
icon-LED
icon-LumiTest
220-240 V 50/60 Hz AC
icon-ProtectionClassII
9003
icon-Through-wiring
Product codeTWS8892WAElectrical number (FI)4280979
GTIN6438045019468TARIC code94056180
Weight0,90 kgMeasurements18,00 × 5,00 × 18,00 cm
Aalto ControlYesBackup (h)Yes
Body materialplasticCE MarkYes
ColourRAL9003Electrical Installation2/3 x 2,5 mm²
EN 60598-2-22YesEscapYes
ETIM classEmergency luminaire (EC001957)Glow Wire Test of Plastic Materials (°C)850
IP ClassIP43Light SourceLED
Lumi TestYesLuminous Flux (lm)80
Max Input Power VA3 VAMountingSurface
Mounting optionPendelNominal Supply Voltage220-240 V, 50/60 Hz AC
Protection ClassIITemperature Range Min - Max (°C)-25...+35
Suitable for Through-WiringYes
Product codeTWS8892WA
Electrical number (FI)4280979
GTIN6438045019468
TARIC code94056180
Weight0,90 kg
Measurements18,00 × 5,00 × 18,00 cm
Aalto ControlYes
Backup (h)Yes
Body materialplastic
CE MarkYes
ColourRAL9003
Electrical Installation2/3 x 2,5 mm²
EN 60598-2-22Yes
EscapYes
ETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)850
IP ClassIP43
Light SourceLED
Lumi TestYes
Luminous Flux (lm)80
Max Input Power VA3 VA
MountingSurface
Mounting optionPendel
Nominal Supply Voltage220-240 V, 50/60 Hz AC
Protection ClassII
Temperature Range Min - Max (°C)-25...+35
Suitable for Through-WiringYes

Scale Images

Scale image

Light Distribution Charts

Emergency lighting for escape routes (ceiling mounting)

  • 1 lux table for the centre line of an escape route, in accordance with EN 1838.
  • Level of measurement 0.02 m, measurement results in emergency mode.
R1 distance from wall, X axis
R2 mounting distance, X axis
R4 distance from wall, Y axis

Emergency lighting for escape routes (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R4 (m)
--1 lx1 lx1 lx
2.5113.581
383.591
44.54101
624111
81.13111

Accessories

Product codeElectrical numberDescription
TW77507B4281135Shock protecting cover TW77507BAdd to cart
TWT92024244125Wall bracket TWT9202Add to cart