Linespot II Lowbay emergency light TWT1471W

24-230 V centrally supplied LED emergency light

The Linespot II Lowbay is a compact and stylish emergency light designed especially for corridor lighting. The luminaire is recess mounted; the size of the recess mounting aperture is Ø 75 mm. Linespot II Lowbay’s design is an unobtrusive solution for energy-efficient emergency lighting.

icon-ce
EN 60598_2_22
650 °C
20
icon-LED
24-230 V 50/60 Hz AC DC
icon-ProtectionClassIII
icon-ProtectionClassI
9003 (Signal white)
icon-Through-wiring
Product codeTWT1471WElectrical number (FI)4281041
GTIN6438045012247TARIC code94056180
Weight0,40 kgMeasurements10,00 × 10,00 × 5,00 cm
Body materialplasticCE MarkYes
ColourRAL9003 (Signal white)Electrical Installation2 x 2,5 mm² (24 V), 3 x 2,5 mm² (230 V)
EN 60598-2-22YesETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)650 IP ClassIP20
Light SourceLEDLuminous Flux (lm)250
Max Input Power VA7,5 VA (24 V), 11 VA (230 V)Max Input Power W4 W (24 V), 4 W (230 V)
MountingRecessNominal Supply Voltage24-230 V, 50/60 Hz AC, DC
Protection ClassIII (24 V), I (230 V)Aperture for Recess Mountingø75
Temperature Range Min - Max (°C)-30...+50Suitable for Through-WiringYes
Product codeTWT1471W
Electrical number (FI)4281041
GTIN6438045012247
TARIC code94056180
Weight0,40 kg
Measurements10,00 × 10,00 × 5,00 cm
Body materialplastic
CE MarkYes
ColourRAL9003 (Signal white)
Electrical Installation2 x 2,5 mm² (24 V), 3 x 2,5 mm² (230 V)
EN 60598-2-22Yes
ETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)650
IP ClassIP20
Light SourceLED
Luminous Flux (lm)250
Max Input Power VA7,5 VA (24 V), 11 VA (230 V)
Max Input Power W4 W (24 V), 4 W (230 V)
MountingRecess
Nominal Supply Voltage24-230 V, 50/60 Hz AC, DC
Protection ClassIII (24 V), I (230 V)
Aperture for Recess Mountingø75
Temperature Range Min - Max (°C)-30...+50
Suitable for Through-WiringYes

Scale Images

Scale image

Light Distribution Charts

Emergency lighting for escape routes (ceiling mounting)

  • 1 lux table for the centre line of an escape route, in accordance with EN 1838.
  • Level of measurement 0.02 m, measurement results in emergency mode.
R1 distance from wall, X axis
R2 mounting distance, X axis
R4 distance from wall, Y axis

Emergency lighting for escape routes (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R4 (m)
--1 lx1 lx1 lx
2.57.59211
4310281
61.59221

Accessories

Product codeElectrical numberDescription
TMT3894280929Gasket ring TMT389Add to cart

How to contact our sales teams

Teknoware Emergency Lighting distributors and sales offices around the world: