Zonespot II Midbay emergency light Y9392WAC

Self-contained Escap Emergency light with 1 h Super Capacitor and Wireless Central Monitoring (Invidually packed TWS9392WAC)

The Zonespot II Midbay is a surface-mounted emergency light. The luminaire’s optics are designed to provide a broad, uniform light pattern that illuminates open areas effectively.
Thanks to the IP44 enclosure class, the Zonespot II is also suitable for damp areas. The luminaire is easy and quick to install thanks to a separate mounting base, which is also connected to the power supply.

icon-AaltoControl
1 h
icon-ce
EN 60598_2_22
icon-Escap
850 °C
43
icon-LED
icon-LumiTest
220-240 V 50/60 Hz AC
icon-ProtectionClassII
9003 (Signal white)
icon-Through-wiring
Product codeY9392WACElectrical number (FI)4280998
GTIN6438045019680TARIC code94056180
Weight1,00 kgMeasurements18,50 × 18,50 × 5,20 cm
Aalto ControlYesBackup (h)Yes
Body materialplasticCE MarkYes
ColourRAL9003 (Signal white)Electrical Installation2/3 x 2,5 mm²
EN 60598-2-22YesEscapYes
ETIM classEmergency luminaire (EC001957)Glow Wire Test of Plastic Materials (°C)850
IP ClassIP43Light SourceLED
Lumi TestYesLuminous Flux (lm)105
Max Input Power VA3 VAMountingSurface
Mounting optionPendelNominal Supply Voltage220-240 V, 50/60 Hz AC
Protection ClassIITemperature Range Min - Max (°C)-25...+35
Suitable for Through-WiringYes
Product codeY9392WAC
Electrical number (FI)4280998
GTIN6438045019680
TARIC code94056180
Weight1,00 kg
Measurements18,50 × 18,50 × 5,20 cm
Aalto ControlYes
Backup (h)Yes
Body materialplastic
CE MarkYes
ColourRAL9003 (Signal white)
Electrical Installation2/3 x 2,5 mm²
EN 60598-2-22Yes
EscapYes
ETIM classEmergency luminaire (EC001957)
Glow Wire Test of Plastic Materials (°C)850
IP ClassIP43
Light SourceLED
Lumi TestYes
Luminous Flux (lm)105
Max Input Power VA3 VA
MountingSurface
Mounting optionPendel
Nominal Supply Voltage220-240 V, 50/60 Hz AC
Protection ClassII
Temperature Range Min - Max (°C)-25...+35
Suitable for Through-WiringYes

Scale Images

Scale image

Light Distribution Charts

Emergency lighting for open areas (ceiling mounting)

  • 0.5 lux table for open areas, in accordance with EN 1838; 0.5-m border zone is taken into account in the table.
  • Level of measurement 0.02 m, measurement result in emergency mode
R1 distance from wall, X axis
R2 mounting distance, X axis
R3 mounting distance, Y axis
R4 distance from wall, Y axis

Emergency lighting for open areas (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R3 (m)R4 (m)
--0.5 lx0.5 lx0.5 lx0.5 lx
2.5112.5552.5
37.52.5552.5
443663
623.5883.5
813.5883.5
Emergency lighting for escape routes (ceiling mounting)

  • 1 lux table for the centre line of an escape route, in accordance with EN 1838.
  • Level of measurement 0.02 m, measurement results in emergency mode.
R1 distance from wall, X axis
R2 mounting distance, X axis
R4 distance from wall, Y axis

Emergency lighting for escape routes (ceiling mounting)

Mounting height (m)Below the light (lx)R1 (m)R2 (m)R4 (m)
--1 lx1 lx1 lx
2.51125.51
37.525.51
44361
6238.51

How to contact our sales teams